HomeMy WebLinkAboutfire safety 2014ITHACA
Town of Ithaca - General Fire Inspection
FtRF
City of Ithaca Fire Department
Activity Date:
04/15/14 02:15:00 PM
v • = - f
310 W Green St
Activity Number:
FI-211-2014-0106
r$ ''
Ithaca, NY 14850
Activity Cause:
Periodic
9ESCU�
Inspector Name:
Nicolas Tier
N.v.
Phone: 607-272-1234
Inspector Phone:
607-272-1234
Fax: 607-272-2793
Status:
Email: firemarshal@cityofithaca.org
Business Name
Occupancy Type:
Top Shelf Liquor
Total Violations:
3
Corrected Violations:
0
821 B DANBY RD Top Shelf Liquor
Hours:
1.0000
Ithaca, NY 14850
Phone:
Address Code:
Building Manager:
A Fire Safety and Property Maintenance Inspection was performed at the location and address indicated above. You are
requested to correct any violations that have been cited. Severe violations must be corrected immediately. All other
violations must be corrected prior to the re -inspection date indicated at the end of this report.
Electrical
5. Junction boxes and Elecrical outlets are properly
covered
Fail
2010 FIRE CODES OF NEW YORK STATE 605.6
Unapproved conditions.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Comment: Outlet in ceiling near the front door the outlet had
no cover on it and did not appear to be seucured .
7. Electrical Panels properly covered
Fail
2010 PROPERTY MAINTENANCE CODE OF NEW
YORK STATE 605.1 Installation.
All electrical equipment, wiring and appliances shall be
properly installed and maintained in a safe and approved
manner.
Comment: Breaker panel in back room had a few slots open.
Slots need to be covered up.
Means of Egress
3. Emergency lights operable and unobstructed
Fail
2010 FIRE CODES OF NEW YORK STATE 604.2.15.3
Emergency systems.
Exit signs, exit illumination as required by Chapter 10, and
elevator car lighting are classified as emergency systems
and shall operate within 10 seconds of failure of the normal
power supply and shall be capable of being transferred to
the standby source. Exception: Exit sign, exit and means of
egress illumination are permitted to be powered by a
standby source in buildings of Group F and S occupancies.
Comment: EM light that is combined with the exit sign over
the front door had enough battery to light sign but not
enough to power lights. Battery or unit needs to be replaced.
Printed Date: 04/15/2014 Page 1 of 2
Business Name
Top Shelf Liquor
821 B DANBY RD Top Shelf Liquor
Ithaca, NY 14850
Phone:
Building Manager:
Occupancy Type:
Total Violations: 3
Corrected Violations: 0
Hours: 1.0000
Address Code:
Nicolas Tier
City of Ithaca Fire Department
310 W Green St
Ithaca, New York14850
607-272-1234
firemarshal@cityofithaca.org
Printed Date: 04/15/2014 Page 2 of 2