HomeMy WebLinkAbout31138___214 Cypress Ct. - Inspection Report 11.01.2023.pdf City of Ithaca Fire Department
%j 310 W Green St
�<< Ithaca, NY 14850
{ -_ Phone: 607-272-1234 Fax:607-272-2793
Town of Ithaca - General Fire Inspection
Inspector Name: Jeff Cook Activity Number: FI-242-2023-0124.A
Inspector Phone: 607-272-1234 Activity Cause: Reinspection
Email: FPBMail@cityofithaca.org Activity Date: 10/05/23 09:00:00 AM
Status: Pass
214 Cypress Court
Atten: TOWN OF ITHACA Occupancy Type: R2 -Apartment/Multi-Dwellin4
Total Violations: 2
214 Cypress Ct Corrected Violations, 2
Ithaca, NY 14850 Hours: 1.00
A Fire Safety and Property Maintenance Inspection was performed at the location and address indicated above. You are
requested to correct any violations that have been cited. Severe violations must be corrected immediately. All other
violations must be corrected within 30 days of this report.
Pre Existing Inspection Details
Reference Number:2020 Fire Code of New York State 901.6.1 Standards.
Fire protection systems shall be inspected.tested and maintained in accordance with the referenced standards listed in Table 901 6 1 (SEE
BOOK)
Corrected On: 11/01/2023
Comment:Sprinkler System due for 5 year internal inspection(NFPA 25).
Reference Number:2020 Fire Code of New York State 906.1 Where required.
Portable fire extinguishers shall be installed in all of the following locations: 1 In new and existing Group A, B. E.F. H. I. M, R-1, R-2, R-4 and S
occupancies Exceptions: 1. In Group R-2 occupancies,portable fire extinguishers shall be required only in locations specified in Items 2 through
6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A:10-13:C.2. In Group E occupancies,
portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each classroom is provided with a portable fire
extinguisher having a minimum rating of 2-A:20-B:C 2 Within 30 feel(9144 mm)distance of travel from commercial cooking equipment and
from domestic cooking equipment in Group 1-1: 1-2,Condition 1:and R-2 college dormitory occupancies 3 In areas where flammable or
combustible liquids are stored. used or dispensed 4 On each floor of structures under construction,except Group R-3 occupancies. in
accordance with Section 3315 1 5 Where required by the sections indicated in Table 906 1 6 Special-hazard areas. including but not limited to
labaatones,computer rooms and generator rooms,where required by the fire code official
Corrected On: 11/01/2023
Comment: Fire Extinguishers are required by code in all apartments-extinguisher size-2A106C.
Jeff Cook
City of Ithaca Fire Department
310 W Green St
Ithaca, New Yorkl4850
607-272-1234
jcook@cityofithaca.org
Printed Date: 11/01/2023 Page 1 of 1